L4008A1015/U Honeywell High Or Low Limit Remote Bulb Aquastat 100-240F

HONL4008A1015 MFG #: L4008A1015/U
  • Installation: Horizontal/Vertical
  • Manufacturer Name: Honeywell
  • Operating Temperature: 100 to 240 Deg F
  • Specifications
  • Documents
  • Description
  • Temperature Controller
  • Bulb Type Copper
  • Voltage Rating 120 to 240 Volt AC
  • Minimum AC Voltage Rating (V) 120 Volt
  • Maximum AC Voltage Rating (V) 240 Volt
  • Minimum DC Voltage Rating (V) 0.25 Volt
  • Maximum DC Voltage Rating (V) 12 Volt
  • Operating Temperature 100 to 240 Deg F
  • Size 2" Width x 2-1/8" Depth x 5-5/8" Height
  • Mounting Horizontal/Vertical
  • Application Boiler, Storage Tank, Duct
  • Approval UL, CSA
  • Contact Rating 5.1 Amp at 240 Volt AC, 8 Amp at 120 Volt AC (Full Load)
  • 30.6 Amp at 240 Volt AC, 48 Amp at 120 Volt AC (Locked Rotor), 0.25 Amp at 0.25 to 12 Volt DC
  • Differential Temperature 5 to 30 Deg F Adjustable
  • Operating Pressure 255 PSI (Immersion Well), 200 PSI (Direct Immersion)
  • Switching Action SPST
  • Bulb Size 3/8" x 2-7/8"
  • Capillary Length 66"
  • Includes Capillary
  • Packaging Quantity 100
  • Weight 1.2 Lb
Aquastat Controllers are Immersion Type Devices for Limiting or Regulating Temperature of Liquids in Boilers or Tanks, can also Sense Duct or Outside Air Temperature; Remote Temperature Sensing Element Detects and Responds Rapidly to Temperature Changes; Totally Enclosed Single Pole Single Throw (Spst) Micro Switch Snap-Acting Switches Operate on Temperature Rise to Set Point; Visible Control Point Scale and External Adjustment Screw Permit Easy Setting; Horizontal or Vertical Mounting of the Remote Element Into Boiler, Tank or other Container Unless Otherwise noted; Case Mounts to a Vertical Surface; Models Calibrated for High Limit use are also Suitable for Low Limit Control if a Separate High Limit Controller is Used; L4008 Include Remote Bulb for Mounting Controller at a Location Away from the Sensing Element; L4008 Provide Spst Switching for High or Low Limit or Circulator Control