- Specifications
- Documents
- Description
- Circulator Pump
- Type Canned Rotor, Compact, Single Head
- Applicable Standard ANSI/UL 778, CAN/CSA C22.2, ETL (Canada and US)
- Suction Size 50 MM
- Discharge Size 50 MM
- End Connection Flanged x Flanged
- Overall Dimensions 15.87" Length x 11.46" Width x 9.45" Height
- Flow Rate 346 GPM
- Discharge Head 80 Decimeter
- Casing Material Cast Iron
- Shaft Material 316L Stainless Steel
- Impeller Material Polyethersulfone
- Warranty 24 Month Limited from Date of Installation, 30 Month Limited from Date of Manufacture
- Power Rating 1/3 HP
- Input Supply Rating 325 Watt at 208 to 230 Volt 50/60 Hertz 1 Phase 1.46 Amp
- Temperature Rating 14 to 230 Deg F
- Pressure Rating 175 PSI
- Motor Type Synchronous, Permanent Magnet, 4 Pole
- Inclusions/Features Aluminum Oxide Bearing Ring, Polycarbonate Control Box, Heat Energy Meter, Intuitive User Interface with TFT Display, Built-In Grundfos Differential Pressure and Temperature Sensor, Internal Motor Protection, Proportional-Pressure Control, Constant-Pressure Control, Constant-Temperature Control, Constant-Curve Duty, Automatic Night Setback
- Application Heating Systems, Air-Conditioning and Cooling Systems, Domestic Hot-Water Systems, Ground Source Heat Pump Systems, Solar-Heating Systems, Heating Surfaces
- Material Aluminum Stator Housing, EPDM O-Ring, Polypropylene Sulfide Rotor Can
- Net Weight 37 Lb
- Gross Weight 45 Lb
Intuitive User Interface with TFT Display; Proportional Pressure Control; Constant Pressure Control; Constant Temperature Control; Built-In Grundfos Differential Pressure and Temperature Sensor; Constant Curve Duty; Automatic Night Setback; In ternal Motor Protection; Heat Energy Meter; In sulating Shells Supplied with Single-Head Pumps for Heating Systems; Unparalleled Energy Efficiency; Safe Selection; Simple Installation; Maintenance Free; Guided Installation; Simple Assisted Troubleshooting; Easy System Optimization; Multi-Pump Function; External Control and Monitoring Enabled Via Add-On Module; No External Motor Protection Required