Y8610U6006/U Honeywell Intermittent Pilot Retrofit Kit

HONY8610U6006 MFG #: Y8610U6006/U
  • Manufacturer Name: Honeywell
  • Specifications
  • Documents
  • Description
  • Ignition Pilot Retrofit Kit
  • Type Electronic, Intermittent Pilot, Universal
  • Fuel Type Natural, LP Gas
  • Flame Sense Type Single/Two Rod
  • Ignition Source Internal High Voltage Spark Generator
  • Ignition Sequence Continuous Retry
  • Ignition Trial Time 15/90 Second
  • Prepurge Time 0/30 Second
  • Flame Failure Response Time 2 Second
  • Valve Rating 1 Amp (Pilot), 2 Amp (Main) at 24 Volt AC
  • Electrical Rating 24 Volt AC at 60 Hertz
  • Size 2-5/8" Length x 5-7/16" Width x 3-15/16" Height
  • Temperature Rating -40 to 165 Deg F
  • Application Gas-Fired Atmospheric Furnaces, Boilers and Heating Appliance
  • Lockout Timing 15/90 Second
  • Includes Gas Valve, Ignition Module, Pilot Burner Hardware, Ignition Cable and Wiring Harness
Complete Kit Converts Conventional Standing Pilot System to an Intermittent Pilot System. for use with 24 Volt Ac Gas-Fired Atmospheric Furnaces, Boiler and Heating Appliances; Y8610U Kit's are for use with Natural or Lap Gas; After 6-Minute Delay, Trial for Ignition is Repeated; Ignition Trail/Delay Sequence is Repeated Until the Appliance Lights or Call for Heat is Removed; Includes Gas Valve, Ignition Module, Pilot Burner Hardware, Ignition Cable and Wiring Harness Provides 100 Percent Pilot Gas Shut-Off if Pilot Fails to Light