TA-350-LF Leonard 3/4" Lead Free Emergency Eye/Face Wash Mixing Valve System With Temperature Override Protection

LEOTA350LFRF MFG #: TA-350-LF-RF
  • End Connection: Sweat
  • Manufacturer Name: Leonard
  • Set Temp Range: 60 to 90 Deg F
  • Valve Size: 3/4"
  • Specifications
  • Documents
  • Description
  • DURA-trol solid bimetal thermostat directly linked to valve porting to control the intake of hot and cold water and compensate for supply temperature and pressure fluctuations. DURA-trol is highly responsive and cannot be damaged by extremes in temperature
  • Primary valve can be set to the correct temperature for the application
  • Locking type temperature regulator to prevent accidental movement set for 85ºF (29ºC)
  • Primary mixing valve will close down on failure of cold water supply
  • Primary Mixing Valve with special internal cold water bypass capable of 4 GPM (15 l/min) @ 30 PSI (2.1 Bar) upon failure of hot water supply
  • Adjustable high temperature limit stop set for 90ºF (32ºC)
  • Full 3/4" top inlets and 3/4" top outlet
  • Integral wall support
  • Dial thermometer (range 0 to 140°F, -10 to 60°C)
  • Rough bronze finish
  • Straight checkstops on inlets
  • Compliance ANSI Z358-1
  • Stainless steel bellows thermostat is factory locked @ 90°F, 32°C (adjustable from (40°F to 100°F), (4°C to 32°C)) to allow cold water to enter the outlet side of the Primary mixing valve
  • Remains fully closed until outlet temperature reaches 90ºF (32ºC)
  • Will keep maximum temperature at or below 90ºF should primary valve allow water in excess of 90ºF (32ºC)
  • Maximum supply temperature 180ºF (82ºC)
  • Maximum supply pressure 125 PSI (8.6 Bar)
DURA-trol solid bimetal thermostat directly linked to valve porting DURA-trol is highly responsive and cannot be damaged by extremes in temperature Primary valve can be set to the correct temperature for the application. Locking temperature regulator to prevent accidental movement set for 85ºF (29ºC) Primary mixing valve will close down on failure of cold water supply. Primary Mixing Valve with special internal cold water bypass capable of 4 GPM (15 l/min) @ 30 PSI (2.1 Bar) upon failure of hot water supply. Adjustable high temperature limit stop set for 90ºF (32ºC) Dial thermometer (range 0 to 140°F, -10 to 60°C) Straight checkstops on inlets Secondary Thermostatic Control factory locked @ 90°F, 32°C(adjustable from 40°F to 100°F, 4°C to 32°C) to allow cold water to enter the outlet side of the primary mixing valve. Rough bronze finish.