AM102-US-1LF/U Honeywell 1" Union Sweat 70-145F Lead Free Mixing Valve

HONAM102US1LF MFG #: AM102-US-1LF/U
  • End Connection: Union Sweat
  • Manufacturer Name: Honeywell
  • Set Temp Range: 70 to 145 Deg F
  • Valve Size: 1"
  • Specifications
  • Documents
  • Description
  • Thermostatic Mixing Valve
  • Type Thermostatic
  • Applicable Standard ASSE 1017, IAPMO, CSA (Canada and US), UPC
  • Nominal Size 1"
  • End Connection Union Soldered x Union Soldered
  • End to End Distance 6.1"
  • Base to Inlet Dimension 3.5"
  • Inlet to Mixing Outlet Dimension 3.5"
  • Body Material Nickel Plated Brass, EPDM O-Ring
  • Flow Rate 0.5 GPM
  • Set Temperature Range 70 to 145 Deg F
  • Temperature Rating 212 Deg F
  • Pressure Rating 150 PSI
  • Inclusions/Features Anti-Scald, Anti-Chill Protection, Tamper Resistant Design, Straight Through Design, Proportional Valve, Replaceable Thermostatic Element, Check Valves on Both Hot and Cold Ports, Non-Stick Coating of Internal Valve Components to Prevent Mineral Build-up and Extend Life
  • High Performance Thermoplastic Proportioning Shuttle
  • Application Automatic Faucets, Combo System, Domestic Water, Green House, Industrial, Nursing Home, Photo Processing, Public Facilities, Radiant Floor Heating, Space Heating, Solar Hot Water, Heat Pump System
  • Lead Free
  • Capacity 3.9 CV
  • Warranty 1 Year Limited
Lead Free; The Honeywell AM-1 Series Accurately Adjusts, Maintains and Limit's the Hot Water Temperature Settings to Provide Comfort and Protect Equipment at Home; While Increasing the Amount of Safe, Usable Hot Water, it Efficiently Offers Anti-Scald, Anti-Chill Protection; By Installing a Honeywell AM-1 Mixing Valve, Raising Water Heater Storage Temperature Setting, and Limiting Mixed Outlet Water Temperature to a Safe Temperature, more Usable Hot Water is Available; Dual Purpose Mixing or Diverting Valves; Constant Water Temperature Under Changing Operating Conditions; Provides Reliable Performance at Minimum Flow of 0.5 GPM and Proportional Valve for Simultaneous Control of Hot and Cold Water; Temperature Limit at any Point and if Cold Water Supply is Interrupted, Flow Reduction Occurs in Seconds; Design for Easy Maintenance and Teflon Coating Prevents Mineral Build-Up and Extends Life; 1 Year Limited Warranty