- Specifications
- Documents
- Description
- Temperature Control Relay
- Voltage Rating 120 Volt AC
- Minimum AC Voltage Rating (V) 120 Volt
- Maximum AC Voltage Rating (V) 240 Volt
- Operating Temperature 110 to 220 Deg F (Low Limit), 130 to 240 Deg F (High Limit)
- Humidity 0 to 95 Percent RH, Non-Condensing
- Size 4-5/16" Width x 3-1/8" Depth x 6-1/8" Height
- Mounting Vertical
- Application Triple Aquastat Relay, Hydronic Heating System
- Approval UL, CSA
- Contact Rating 7.4 Amp at 120 Volt AC, 3.7 Amp at 240 Volt AC (Full Load), 44.4 Amp at 120 Volt AC, 22.2 Amp at 240 Volt AC (Locked Rotor)
- Differential Temperature Rating 10 Deg F Fixed (High Limit), 10 to 25 Deg F (Low Limit)
- Operating Pressure 200 PSI (Immersion Well)
- Switching Action SPST
Immersion Type Controllers that Combine High Limit Protection with Low Limit and Circulator Control in Forced Hydronic Heating Systems, Including Domestic Hot Water Service; Provide Multizone Control by Using a Separate Circulator and R845 Relay for Each Zone; Include Diaphragm Power Head and Micro Switch Assembly that Respond to Temperature Changes in Boiler Water, Mount Directly to Boiler; Select Models Include Large Transformers and Extra Terminals for Supplying Power to Low Voltage Zone Valves; Require 24 Volt Ac Thermostat with Heat Anticipator Set at 0.2 Amp (Plus Current Draw of Gas Valve on L8124E); Trade Line Models Include Tube of Heat Conductive Compound and Range Stops