- Specifications
- Documents
- Description
- Ignition Control Module
- Type Electronic, Direct Spark, Pilot
- Fuel Type Natural, LP Gas
- Flame Sense Type Single Rod
- Ignition Source Internal High Voltage Spark Generator
- Ignition Sequence Single Trial
- Ignition Trial Time 11 Second
- Prepurge Time None
- Flame Failure Response Time 0.8 Second
- Valve Rating 2 Amp at 24 Volt AC
- Electrical Rating 24 Volt AC at 60 Hertz
- Size 1-15/16" Length x 4-1/16" Width x 5-1/4" Height
- Temperature Rating -40 to 147 Deg F
- Application Gas-Fired Furnaces, Boilers, and Other Heating Appliances
- Approval CSA
- Lockout Timing 11 Second
- Flame Failure Re-Ignition Time 0.8 Second Maximum
Provide Electronic Control of Direct Spark Ignition Systems Used on Gas Fire Furnaces, Boilers and other Heating Appliances; Control Ignition Sequence and Gas Control Operation; Generate High Voltage Potential for Main Burner Ignition; Lockout After One Trial for Ignition if Main Burner Fails to Ignite; Reset from Thermostat After Lockout