TA-300-LF Leonard 1/2" Lead Free Single Emergency Eye/Face Wash Mixing Valve

LEOTA300LFRF MFG #: TA-300-LF-RF
  • End Connection: Sweat
  • Manufacturer Name: Leonard
  • Set Temp Range: 40 to 100 Deg F
  • Valve Size: 1/2"
  • Specifications
  • Documents
  • Description
  • DURA-trol solid bimetal thermostat directly linked to valve porting to control the intake of hot and cold water and compensate for supply temperature and pressure fluctuations
  • DURA-trol is highly responsive and cannot be damaged by extremes in temperature
  • Thermostatic Mixing Valve can be set to the correct temperature for the application
  • Locking temperature regulator to prevent accidental movement set for 85°F (29°C)
  • Mixing valve will close down on failure of cold water supply
  • Mixing valve with special internal cold water bypass capable of a minimum of 4 GPM (15 l/min) @ 30 PSI (2.1 Bar) upon failure of hot water supply
  • Adjustable high temperature limit stop set for 90°F (32°C)
  • Integral wall support
  • Sweat 1/2" top or bottom inlets
  • Threaded 1/2" top outlet
  • Rough bronze finish
  • Dial thermometer (range 0 to 140°F, -10 to 60°C)
  • Angle checkstops on inlets
  • Compliance ANSI Z358.1
  • Maximum supply temperature 180 °F (82°C)
  • Maximum supply pressure 125 PSI (8.6 Bar)
ECO-MIX DURA-trol solid bimetal thermostat directly linked to valve porting to control the intake of hot and cold water and compensate for supply temperature and pressure fluctuations. DURA-trol is highly responsive and cannot be damaged by extremes in temperature. Thermostatic Mixing Valve can be set to the correct temperature for the application. Locking type temperature regulator to prevent accidental movement set for 85ºF (29ºC), Recommended Hot Inlet Temperature 140°F. Mixing valve will close down on failure of cold water supply, Mixing Valve with special internal cold water bypass capable of 4 GPM (15 l/min) @ 30 PSI (2.1 Bar) upon failure of hot water supply. Adjustable high temperature limit stop set for 90ºF (32ºC), Full 1/2" top or bottom inlets and 1/2" top outlet, Integral wall support, Dial thermometer (range 0 to 140ºF, -10 to 60ºC), Rough bronze finish. Union angle checkstops on inlets To determine the amount of Hot Water needed to maintain a steady outlet temperature for 15 minutes.