- Specifications
- Documents
- Description
- Hydronic Low Water Cut-Off
- Item Low Water Cut-Off
- Type Probe
- Applicable Standard UL
- Port Connection 3/4" Female Threaded
- Actuation Type Electronic
- Overall Dimensions 6-5/8" Length x 5-5/16" Height
- Input Supply Rating 50 VA at 24 Volt AC
- Temperature Rating 250 Deg F Water
- Pressure Rating 150 PSI Steam, 160 PSI Water
- Media Handled Steam, Water
- Inclusions/Features Green Power on Indicating LED, Red Low Water Indicating LED, Test Button
- Application Commercial, Industrial
- Probe Sensitivity 20000 Ohm
- Weight 2.5 Lb
Primary or Secondary Control on Hot Water Boilers; No Lock Out with Loss of Power if Probe is in Water