LV3403B44R Rego Backmount Regulator 2nd Stage 1/2" F.NPT X 1/2" F.NPT 11" w.c. 9"-13" w.c. Vent Over Inlet 450,000 BTU/hr
REGLV3403B44R
MFG #: LV3403B44R
- BTU Capacity: 450,000 BTU/Hr
- Inlet Size: 1/2"
- Manufacturer Name: Rego
- Orifice Size: 7/32”
- Outlet Pressure: 11" w.c.
- Outlet Size: 1/2"
- Pressure Range: 9"-13" w.c.
- Type: Regulator
- Vent Position: Over Inlet
- Specifications
- Documents
- Description
- Built in 1/8" F.NPT pressure taps on both regulator inlet and outlet side of the regulator. Plugs can be removed with a 3/16" hex Allen wrench
- Large vent helps prevent vent blockage, it is tapped for 3/8" F.NPT for vent pipe away applications.
- With 15 PSIG inlet pressure, the regulator is designed to not pass more than 2 PSIG downstream with the seat disc removed per UL 144 specifications
- Incorporates an integral relief valve per UL 144 specifications
- Unique bonnet vent profile minimizes vent freeze over
- Compact design saves space
The LV3403BR Back Mount Regulator Is Designed To Reduce First Stage Pressure Of 5-10 PSIG Down To Burner Pressure Normally 11" W.C. Designed As A Second Stage Regulator For Smaller Applications With Flow Requirements Up To 450,000 BTU/Hr. And Are Ideal For Homes, Mobile Homes, And Cottages.