- Specifications
- Documents
- Description
- Heat loss at 21C (W/m): 6.7
- Heat loss at 70F (BTU/hr ft): 6.968
- Linear expansion rate (inch/10F/100ft): 1.1
- Linear expansion rate (mm/5.56C/30.48m): 27.94
- Material: PEX
- Material insulation: Polyethylene foam
- Material service pipe: Crosslinked polyethylene (PEX: a) tubing
- SDR: 9, with EVOH oxygen barrier that conforms to DIN 4726
- Operating Pressure 1 (psi): 160 psi
- Operating Pressure 2 (psi): 100 psi
- Operating Pressure 3 (psi): 80 psi
- Operating Temperature 1 (F): 73 F
- Operating Temperature 2 (F): 180 F
- Operating Temperature 3 (F): 200 F
- Thermal conductivity pipe (BTUin/fthrF): 0.22
- Thermal conductivity pipe (W/mK): 0.0317 (PEX)
Uponor's pre-insulated PEX pipe offering complies with ASHRAE 90.1-2013 and the 2012 International Energy Conservation Code (IECC). The pipe is available in 1/2" to 2" configurations with 1/2", 1", 11/2" and 2" insulation that features manufactured sealed seams that run the entire length of the coil. Check with local code authorities regarding energy-code requirements for specific applications.